The effect of low ventilation rate with elevated bioeffluent concentration on work performance, perceived indoor air quality, and health symptoms
Tekijät: Henna Maula, Valtteri Hongisto, Viivi Naatula, Annu Haapakangas, Haanu Koskela
Kustantaja: Wiley-Blackwell Publishing, Inc.
Julkaisuvuosi: 2017
Journal: Indoor Air
Vuosikerta: 27
Numero: 6
Aloitussivu: 1141
Lopetussivu: 1153
Sivujen määrä: 13
ISSN: 0905-6947
eISSN: 1600-0668
DOI: https://doi.org/10.1111/ina.12387
The aim of this laboratory experiment was to study the effects of ventilation rate, and related changes in air quality, predominantly bioeffluents, on work performance, perceived indoor air quality, and health symptoms in a typical conditions of modern open-plan office with low material and equipment emissions. In Condition A, outdoor air
flow rate of 28.2 l/s person (CO2 level 540 ppm) was applied and in Condition B, outdoor
air flow rate was 2.3 l/s person (CO2 level 2260 ppm). CO2 concentration level
was used as an indicator of bioeffluents. Performance was measured with seven different tasks which measure different cognitive processes. Thirty-six subjects participated in the experiment. The exposure time was 4 hours. Condition B had a weak negative effect on performance only in the information retrieval tasks. Condition B increased slightly subjective workload and perceived fatigue. No effects on health symptoms were found. The intensity of symptoms was low in both conditions. The experimental condition had an effect on perceived air quality and observed odor intensity only in the beginning of the session. Although the room temperature was controlled in both conditions, the heat was perceived to impair the performance more in Condition B.