A4 Refereed article in a conference publication

Extremely Low Frequency Magnetic Fields at Electric Facilities of a Hospital




AuthorsVahekoski T, Sankari J, Seppälä T, Korpinen L

Conference nameProgress in Electromagnetic Research Symposium (PIERS)

Publication year2016

Book title 2016 Progress in Electromagnetic Research Symposium (PIERS)

Journal name in source2016 PROGRESS IN ELECTROMAGNETICS RESEARCH SYMPOSIUM (PIERS)

First page 1413

Last page1415

Number of pages3

ISBN978-1-5090-6094-8

eISBN978-1-5090-6093-1

DOIhttps://doi.org/10.1109/PIERS.2016.7734665


Abstract
This paper presents the investigation of extremely low frequency magnetic fields at electric facilities of a hospital. We conducted 21 measurements (at electric facilities and other areas, for example, in the lobby and in the corridor). The magnetic fields were from 0.2 mu T to 62.0 mu T. The highest value was measured near the main circuit-breaker of the distribution board. Based on the measurements, the magnetic fields can be more than 50 mu T in the technical areas of a hospital, which can cause disturbances in some medical devices.



Last updated on 26/11/2024 09:47:25 PM